Axis Network I/O Relay - Controlling using HTTP commands

The steps in this article require using the web interface of a 2N device. Please follow this manual in case this is your first time using the web interface.

 

Prerequisities

  • 2N IP Intercom, 2N Access Unit or 2N Indoor Station with the latest firmware
    • Additional GOLD license is neccessary for 2N IP intercom
  • AXIS A9210 Network I/O Relay Module (Order numbers: 2N - 1120303, Axis - 02861-001) - 1 Relay Output


1120303  

  • AXIS A9910 I/O Relay Expansion Module (Order numbers: 2N - 1120304, Axis - 02862-001) - 4 Relay Output


1120304A  

 

Finding the device in the network

The following steps help you find the Axis device on your network
  • Install and run the 2N IP Utility

  • Make sure that you are on the same network as the Axis I/O Relay Module

  • Locate the Axis I/O Relay Module in the device list and click on the IP Address (1)

  • Then, click on the "Load web interface" button (2)

Axis Relay Search

  • If you are configuring a brand new device or device that has been reset to Factory Defaults, create a new Account and fill out the password (3)

Axis Relay Account Creation

 

  • Lastly, log into the unit (4), using the created credentials

Axis Relay Login  

 

 

Connecting and configuring the Axis I/O Relay Modules

The following article shows details about AXIS Relay configuration, operation and interconnection between the AXIS A9210 and AXIS A9910

A9210

Detailed manual can be found here

  • Go under the "Device" tab and "I/Os and relays" (1)

  • You can check the general Relays overview - change it's name, enable or disable it manually (2)

  • Under "Toggle port URL" you can see ON and OFF HTTPS commands (3)

A9210  

A9910

Detailed manual can be found here

  • First, connect the A9910 Extending Relay Module to the main A9210 Relay Module using the picture below

Interconnection  
Follow closely the interconnection shown above (GND -> GND, A -> A, B -> B), use only the shown connectors RS485 (on AXIS A9210) and EXP IN (on AXIS 9910)
  • Next, set the desired Address of the A9910 Extending Relay Module on the DIP Switch connector according to this chart:

DIP SWITCH

  • Go under the Device tab and I/Os and relays (1)

  • Select the AXIS A9910 (2)

  • An Encryption Key (3) has to be generated in order to add the AXIS A9910

A9910 1

 

  • You can generate the Encryption Key by pressing the Generate Key button (5)

  • You can also export the Encryption Key (6)

  • Then click OK (7) and proceed further

Encryption key

  • Make sure that the Encryption enabled (8) is showing

  • Then click on the Add AXIS A9910 (9) button

  • Lastly, select a name, used RS485 port, and module Address - as selected on the DIP switch of the device, then hit Save (10)

A9910 2

  • Once added the expansion module will list the available I/O ports, relays, it's name, address, serial number and upgrade button (11)

  • You can check the general Relays overview - change it's name, enable or disable it manually (12)

  • Under Toggle port URL you can see ON and OFF HTTPS commands (13)

A9910 3 

     

    Controlling the Axis I/O Relay Module from 2N Units

    How to control the Axis device from 2N Units
    • Detailed API Commands can be found in the VAPIX Library

    • AXIS A9210 Network I/O Relay (1120303 A)

      ONhttps://192.168.1.2/axis-cgi/io/port.cgi?action=1%3A%2F
      OFFhttps://192.168.1.2/axis-cgi/io/port.cgi?action=1%3A%5C
      ON for 2 Secondshttp://192.168.1.2/axis-cgi/io/port.cgi?action=1%3A%2F2000%5C

     

    Sending HTTP commands to AXIS Network I/O Relay by 2N IP intercom or 2N Access Unit

    Firmware 3.0+
    • Login to 2N IP Intercom web interface, section Integration and Switches (1) and select the desired Switch 1-4 (2)

    • Set up the time limit for the switch to activate by adjusting the Switch-On Duration, under the Configuration (3)

    New Firmware Command configuration

    • Then under the HTTP Commands set up the Switch-On / Switch-Off HTTP Commands and enter the Login credentials of the AXIS Network I/O Relay, then use the commands from the previous table (4) and save

    Latest firmware switch configuration



      

     

    Firmware 2.50 (LTS):
    • Login to 2N IP Intercom web interface, section Hardware (1), then select the Switches (2) and lastly select the desired Switch 1-4 (3)

    • Set up the time limit for the switch to activate by adjusting the Switch-On Duration (4)

    • Then under the HTTP Commands set up the Switch-On / Switch-Off HTTP Commands and enter the Login credentials of the AXIS Network I/O Relay, then use the commands from the previous table (5) and save.

    2N IP intercom - Hardware - Switches - HTTP Commands

    • Now every time when the 2N IP Intercom's switch is activated, the AXIS Network I/O Relay is triggered on and after 1 second triggered off.
      More information about Switch settings in our manual: 2N IP Intercom - Configuration manual

     

       

      Sending a HTTPS Command to the 2N Units from AXIS Relay Module when Input is triggered

      The following article shows how to set up the AXIS Relay Module to send a HTTPS command to 2N Units

      Please refer to the 2N HTTP API guide here

      • First, select the System (1) tab, then Events (2) tab

      • Next select the Recipients tab and click on Add recipient (3)

      Recipients  

      • Fill out the window accordingly with the corresponding name, connection type, URL and HTTP API account credentials (4) of the 2N Unit - see manual here

      • Lastly confirm with Save (5)

      Recipient setup

      • Next, select the previous window under System and Events - Rules and click on the Add a rule (6)

      Rule adding

      • Select a name (7)

      • Choose a condition (8) from the list, you wish to send the HTTPS command to the 2N Unit when it is fulfilled

      • Select a port on the AXIS A9210 (ports from connected AXIS A9910 can be selected as well) (9)

      • Choose an action and recipient (10) from the list

      • Next select the corresponding query string suffix (for 2N Units available here) and a method (11)

      • Lastly confirm with Save (12) 

      • Now, when the corresponding condition is met, the action will be performed - Input activated -> 2N Unit receives into it's Automation HTTP Trigger with ID "BEEP" - it will play a sound *1"Modern Ringtone"

      Automation

       

       